MULTISHRINK Heat Shrinkable Transition Joints for 11 KV
MULTISHRINK present our collection of heat shrinkable transition joints that are suitable for medium voltage to high voltage applications upto 36 KV. Our heat shrinkable products are designed keeping in mind the special requirements of our esteemed customers. These are supplied with all the tubing and interconnectivity components necessary to quickly and easily complete installations.
|
|
Heat Shinkable Terminations Suitable for 3 Core Paper Insulated Lead Covered MIND Cable for UPTO 11 KV
|
|
Test
|
Requirement
|
Typical Value
|
|
A.C. Dry Withstand Voltage
|
35 KV/1 Minute
|
Pass
|
|
D.C. Voltage Withstand Test
|
48 KV/15 Minute
|
Pass
|
|
Lightening Impulse withstand Voltage
|
75 KV
|
> 75 KV
|
|
Ordering Information
|
|
Cable Size (Sq mm)
|
Kit Code 11 KV
|
|
16-35
|
MKXL-TJ-11
|
|
50-95
|
MKXL-TJ-12
|
|
120-185
|
MKXL-TJ-13
|
|
240-400
|
MKXL-TJ-14
|
|
MULTISHRINK Heat Shrinkable Straight Through Joints & Transition
Heat Shrinkable Straight Through Joint Suitable for 11 KV 3 Core PILC Cables & TRANSISTION JOINT
|
Heat Shinkable Terminations Suitable for 3 Core Paper Insulated Lead Covered MIND Cable for 24 KV
|
|
Test
|
Requirement
|
Typical Value
|
|
A.C. Dry Withstand Voltage
|
50 KV/1 Minute
|
Pass
|
|
D.C. Voltage Withstand Test
|
96 KV/15 Minute
|
Pass
|
|
Lightening Impulse withstand Voltage
|
125 KV
|
> 125 KV
|
|